Transformer Sizing Calculator

Transformer Sizing Calculator

Select the correct transformer kVA rating for multiple loads with demand factor and growth

Results

Total Connected Load
Design Load (with demand+growth)
% Loading at Recommended Size
Total kW
Recommended: — kVA

Formula Reference

Each Load kVA = Load kW / Power Factor
Total Connected kVA = Σ (Load_i kW / PF_i)
Design kVA = Total kVA × (Demand Factor / 100) × (1 + Growth / 100)

Standard Sizes (kVA): 15, 25, 37.5, 45, 50, 75, 100, 112.5, 150,
167, 225, 300, 500, 750, 1000
Recommended = next standard size ≥ Design kVA
% Loading = Design kVA / Recommended kVA × 100

Worked Example

Three loads: HVAC (50 kW, PF=0.85), Lighting (30 kW, PF=1.0), Motors (40 kW, PF=0.80). Demand factor 90%, Growth 25%.

LoadkWPFkVA
HVAC500.8558.8
Lighting301.0030.0
Motors400.8050.0
Total120 kW138.8 kVA
Design kVA138.8 × 0.90 × 1.25 = 156.1 kVA
Recommended167 kVA transformer (93.5% loading)