Fan Laws Calculator — Airflow, Pressure & Power at New Speed | Engineering Calc Pro

💨 Fan Laws Calculator

Airflow, pressure & power at new speed or wheel diameter

Results at New Speed

Speed Ratio
N₂/N₁
New Airflow Q₂
CFM
New Pressure SP₂
in w.g.
New Power BHP₂
HP

Fan Laws (same as pump affinity laws)

Q₂ = Q₁ × (N₂/N₁)  (flow ∝ speed)

SP₂ = SP₁ × (N₂/N₁)²  (pressure ∝ speed²)

BHP₂ = BHP₁ × (N₂/N₁)³  (power ∝ speed³)

📝 Worked Example

Fan at 1200 RPM: 10,000 CFM, 2.5 in w.g., 8 BHP. Reduce to 900 RPM for part-load.

Ratio = 900/1200 = 0.75

Q₂ = 10,000 × 0.75 = 7,500 CFM  |  SP₂ = 2.5 × 0.75² = 1.41 in w.g.

BHP₂ = 8 × 0.75³ = 3.38 BHP  →  57.8% power saving!

7,500 CFM  |  1.41 in w.g.  |  3.38 BHP