Power Factor / kVAR Calculator

Power Factor / kVAR Calculator

Find power factor and reactive power, or calculate capacitor bank size for correction

Results

Power Factor
Reactive Power Q (kVAR)
Phase Angle θ

Results

Capacitor Bank (kVAR)
New Apparent Power (kVA)
Current Reduction

Formula Reference

Power Triangle: S² = P² + Q²
PF = P / S = cos(θ)
Q = √(S² − P²) = P × tan(θ)
θ = arccos(PF)

Power Factor Correction:
Q_cap = P × (tan(arccos(PF₁)) − tan(arccos(PF₂)))
S_new = P / PF₂
Current reduction % = (1 − PF₁/PF₂) × 100

Worked Example

A facility draws 100 kW at 0.75 PF. Target PF = 0.95.

ParameterValue
Original kVA100 / 0.75 = 133.3 kVA
Original kVAR√(133.3²−100²) = 88.2 kVAR
Capacitor bank needed100×(tan(arccos(0.75))−tan(arccos(0.95))) = 54.3 kVAR
New kVA100 / 0.95 = 105.3 kVA
Current reduction≈ 21%